PRTG Manual: SNMP UPS Status Sensor

The SNMP UPS Status sensor monitors the status of an uninterruptible power supply (UPS) via Simple Network Management Protocol (SNMP).

i_betaThis sensor is in beta status. The operating methods and the available settings are still subject to change. Do not expect that all functions work properly, or that this sensor works as expected at all.

SNMP UPS Status Sensor

SNMP UPS Status Sensor

i_square_cyanFor a detailed list and descriptions of the channels that this sensor can show, see section Channel List.

Sensor in Other Languages

  • Dutch: SNMP UPS Status
  • French: SNMP UPS Status
  • German: SNMP USV-Zustand
  • Japanese: SNMP UPS Status
  • Portuguese: SNMP UPS Status
  • Russian: SNMP UPS Status
  • Simplified Chinese: SNMP UPS Status
  • Spanish: SNMP Estado del UPS

Remarks

Consider the following remarks and requirements for this sensor:

Requirement

Description

Enabled Beta Sensors experimental feature

This sensor requires that the Beta Sensors experimental feature is enabled.

i_square_cyanFor more information, see the Knowledge Base: What are beta sensors and how can I use them?

Credentials

This sensor requires credentials for SNMP in settings that are higher in the object hierarchy.

SNMP v2c or SNMP v3

We recommend that you select SNMP v2c (most common) or SNMP v3 in the credentials for SNMP devices of the parent device (if supported by the target device). SNMP v1 does not support 64-bit counters, which might result in invalid data. For more information, see the Knowledge Base: SNMP Traffic sensor suddenly drops at 610Mbps

Localhost

It might not work to query data from a probe device via SNMP (querying localhost, 127.0.0.1, or ::1). Add this device with the IP address that it has in your network and create the sensor on this device instead.

IPv6

This sensor supports IPv6.

Performance impact

This sensor has a very low performance impact.

Lookups

This sensor uses lookups to determine the status values of one or more channels.

Scanning interval

The recommended scanning interval of this sensor is 1 minute.

Multi-platform probe

You can add this sensor to a multi-platform probe.

Basic Sensor Settings

Basic Sensor Settings

Basic Sensor Settings

The sensor has the following default tags that are automatically predefined in the sensor's settings when you add the sensor:

  • battery
  • snmp
  • ups

i_square_cyanFor more information about basic sensor settings, see section Sensor Settings.

Sensor Display

Sensor Display

Sensor Display

Setting

Description

Primary Channel

Select a channel from the list to define it as the primary channel. In the device tree, PRTG displays the last value of the primary channel below the sensor's name. The available options depend on what channels are available for this sensor.

i_round_blueYou can set a different primary channel later by clicking b_channel_primary below a channel gauge on the sensor's Overview tab.

Graph Type

Define how this sensor shows different channels:

  • Show channels independently (default): Show a graph for each channel.
  • Stack channels on top of each other: Stack channels on top of each other to create a multi-channel graph. This generates a graph that visualizes the different components of your total traffic.
    i_round_redYou cannot use this option in combination with manual Vertical Axis Scaling (available in the channel settings).

Stack Unit

This setting is only visible if you select Stack channels on top of each other above.

Select a unit from the list. PRTG stacks all channels with this unit on top of each other. By default, you cannot exclude single channels from stacking if they use the selected unit. However, there is an advanced procedure to do so.

Debug Options

Debug Options

Debug Options

Setting

Description

Result Handling

Define what PRTG does with the sensor result:

  • Discard result (default): Do not store the sensor result.
  • Store result: Store the sensor result and the last response in the \Logs\sensors subfolder of the PRTG data directory on the probe system. The file name is Result of Sensor [ID].log. This setting is for debugging purposes. PRTG overwrites this file with each scanning interval.

i_podThis option is not available when the sensor runs on the hosted probe of a PRTG Hosted Monitor instance.

i_round_blueIn a cluster, PRTG stores the result in the PRTG data directory of the master node.

Inherited Settings

By default, all of these settings are inherited from objects that are higher in the hierarchy. We recommend that you change them centrally in the root group settings if necessary. To change a setting for this object only, click b_inherited_enabled under the corresponding setting name to disable the inheritance and to display its options.

i_square_cyanFor more information, see section Inheritance of Settings.

Channel List

i_round_blueWhich channels the sensor actually shows might depend on the target device, the available components, and the sensor setup.

Channel

Description

Battery Status

The battery status

  • Up status: Battery Normal
  • Warning status: Battery Low, Unknown
  • Down status: Battery Depleted
  • Unknown status: Channel Value Not Set

i_round_blueThis channel is the primary channel by default.

Charge Remaining

The remaining charge (%)

i_round_blueThis channel has default limits:

  • Lower error limit: 20%
  • Lower warning limit: 50%

Current Load

The current load (%)

Downtime

In the channel table on the Overview tab, this channel never shows any values. PRTG uses this channel in graphs and reports to show the amount of time in which the sensor was in the Down status.

Estimated Time Remaining

The estimated remaining time until the UPS reaches 0%

More